Vcm-x expansion module wiring, Output wiring, Vcm-x component & systems wiring – Orion System VCM-X E-BUS Component User Manual

Page 43: Warning, 24 vac gnd, Copeland digital compressor wiring detail, Vcm-x expansion module

Advertising
background image

VCM-X Component & Systems Wiring

VCM-X Expansion Module Wiring

43

Output Wiring

Figure 24: OE333-23-EM - VCM-X Expansion Module Output Wiring

FILENAME

DATE:

S. Olson

DESCRIPTION:

PAGE

JOB NAME

VCMX-Exp-Outputs-1B.CDR

1 of 1

01/11/13

VCM-X Expansion Module

Output

Wiring

REVISED:

S. Olson

05/14/15

24 VAC

GND

10 VA Minimum

Power Required For

VCM-X Expansion

Module

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and
24VAC-to-24VAC. Failure to observe polarity will result in damage to
one or more of the boards. Expansion Modules must be wired in
such a way that the expansion modules and the controller are
always powered together. Loss of power to the expansion module
will cause the controller to become inoperative until power is
restored to the expansion module.

Copeland Digital

Compressor Controller

P4

RD

WH

BK

P3

P2

P1

SHLD

EXC

OUT

COM

P5

P6

C1

C2

Suction Pressure

Transducer

1.) If Unit Has Dehumidification Option And Copeland Digital
Compressor Is Used, Wire Suction Pressure Transducer To Copeland
Controller As Shown.

2.) The Modulating Cooling Output Voltage Must Be Configured For 1.5
- 5 VDC Operation When You Are Setting Up The VCM-X Controller
Operating Parameters For The Copeland Digital Compressor.

Note:

COM

COM

COM

+

+

+

Modulating Heating
(0 to 10 VDC Input)

Building Pressure

Relief Fan VFD

Building Pressure Control

Damper Actuator

Modulating Cooling

Or Digital Scroll Compressor

(1.5 To 5, 0 To 10 Or 2 To 10 VDC Input)

Return Air Bypass

Damper Actuator

(0-10 VDC)

Return Air

Damper Actuator

(0-10 VDC)

Configurable Relay Output #1

R1

R2
R3
R4

Configurable Relay Output #2
Configurable Relay Output #3
Configurable Relay Output #4

Belimo Actuator Wiring

Shown. Consult Factory

For Other Manufacturer

Wiring Instructions

When Copeland
Digital Compressor
Is Used, Wire Per
Copeland Digital
Compressor Wiring
Detail

Either A Building Pressure
Damper Actuator Or a
Building Pressure Relief
Fan VFD Can Be Used,

Copeland Digital Compressor Wiring Detail

3 Y1

3 Y1

3 Y1

2 +

2 +

2 +

1 COM

1 COM

1 COM

Note:
1.) The Modulating
Cooling Device Used
Must Be Capable Of
Accepting Either A 0-10
VDC, 2-10 VDC or 1.5-
5.0 VDC Input. The
Modulating Cooling
Output Voltage Is User
Configurable For These
Voltages. The
Modulating Heating
Devices Used Must Be
Capable of Accepting
Either A 0-10 VDC or 2-
10 VDC Input. The
Modulating Heating
Output Voltage Is User-
Configurable For These
Voltages. These Voltage
Outputs Must Also Be
Configured When You
Are Setting Up The
VCM-X Controller(s)
Operating Parameters.

2.) Each Modulating
Heating Or Cooling
Device Used On The
VCM-X Controller Must
Have (1) Relay Output
Configured For Each
Device Used, In Order
To Enable The
Modulating Heating
And/Or Cooling Device's
Sequence. This Relay
Output Must Be
Configured When
Setting Up The VCM-X
Controller Operating
Parameters.

Relay Output Contacts R1 Through R4 May
Be User-Configured For The Following:

Note:

-

1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel
13 - Emergency Heat

A Total Of 20 Relays Are Available By

Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.

Note:
All Relay Outputs Are Normally
Open And Rated For 24 VAC
Power Only. 1 Amp Maximum
Load.

VCM-X Expansion

Module

A 1

O

AO2

AO3

AO4

AO5

GND

GND

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RELAY 2

RELAY 1

RELAY 3

RELAY 4

RELAY
COMMON

I2C

EXPANSION

I2C

EXPANSION

AO1 = BUILDING PRESSURE CONTROL VFD OR

DAMPER ACTUATOR (0-10 OR 2-10 VDC)

= MODULATING HEATING SIGNAL

(0-10 VDC OR 2-10 VDC)

= MODULATING COOLING/DIGITAL SCROLL

SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)

= RETURN AIR DAMPER ACTUATOR

(0-10 VDC)

= RETURN AIR BYPASS DAMPER ACTUATOR

(0-10 VDC)

= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS

AO2

AO3

AO4

AO5

GND

GND

BI1 = HOOD ON - N.O. INPUT

BI2

BI3

BI4

BI5

BI6

BI7

BI8

= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= SMOKE DETECTOR - N.C. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT

ANALOG INPUT

JUMPER SETTINGS

MUST BE SET AS

SHOWN FOR

PROPER

OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE
OBSERVED OR THE BOARD
WILL BE DAMAGED

www.orioncontrols.com

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

ANALOG INPUT

JUMPER

SETTINGS

RELAY 1 =

RELAY 3 =

RELAY 2 =

RELAY 4 =

IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)

WattMaster Label

#LB102034-01

NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.

AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)

AI2

AI3

AI4

GND

GND

= INDOOR AIR RH SENSOR (0-5 VDC)
= CO2 (0-10 VDC)
= BUILDING STATIC PRESSURE (0-5 VDC)

= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS

+V

SIG

GND

PR OUT

GND

SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR

TO VCM-X INPUT
TERMINALS AI5 & GND

OE333-23-EM-A VCM-X EXPANSION MODULE

VCM

WA

RN

IN

G

OB

SE

RV

E

POLAR

IT

Y

Modular Cable

Connect To VCM-X

E-BUS Controller

Modular Cable

Connect To Next Expansion

Board (When Used)

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RELAY 2

RELAY 1

RELAY 3

RELAY 4

RELAY
COMMON

I2C

EXPANSION

I2C

EXPANSION

AO1 = BUILDING PRESSURE CONTROL VFD OR

DAMPER ACTUATOR (0-10 OR 2-10 VDC)

= MODULATING HEATING SIGNAL

(0-10 VDC OR 2-10 VDC)

= MODULATING COOLING/DIGITAL SCROLL

SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)

= RETURN AIR DAMPER ACTUATOR

(0-10 VDC)

= RETURN AIR BYPASS DAMPER ACTUATOR

(0-10 VDC)

= GROUND FOR ANALOG OUTPUTS
= GROUND FOR ANALOG OUTPUTS

AO2

AO3

AO4

AO5

GND

GND

ANALOG INPUT

JUMPER SETTINGS

MUST BE SET AS

SHOWN FOR

PROPER

OPERATION

24 VAC POWER
ONLY

WARNING!
POLARITY
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED

AI1

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

ANALOG INPUT

JUMPER

SETTINGS

RELAY 1 =

RELAY 3 =

RELAY 2 =

RELAY 4 =

IT IS SUGGESTED
THAT YOU WRITE THE
DESCRIPTION OF
THE RELAY OUTPUTS
YOU ARE USING IN
THE BOXES
PROVIDED ABOVE
WITH A PERMANENT
MARKER (SHARPIE®)

WattMaster Label

#LB102034-01-A

Rev.: 1L

NOTE:
ALL BINARY INPUTS MUST BE 24 VAC ONLY.

+V

SIG

GND

PR OUT

GND

SUCTION PRESSURE
TRANSDUCER CONNECTION
FOR HVAC UNITS WITHOUT
DIGITAL COMPRESSOR

TO VCM-X INPUT
TERMINALS AI5 & GND

BI1 = EMERGENCY SHUTDOWN - N.C. INPUT

= DIRTY FILTER - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
= REMOTE FORCED COOLING - N.O. INPUT
= HOOD ON - N.O. INPUT
= REMOTE DEHUMIDIFICATION - N.O. INPUT

BI2

BI3

BI4

BI5

BI6

BI7

BI8

www.aaon.com

www.orioncontrols.com

VCM-X Expansion Module

Orion No.:OE333-23-EM

AAON No.:

R69190

AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)

AI2

A3

AI4

GND

GND

= INDOOR AIR RH SENSOR (0-5 VDC)
= ECONOMIZER FEEDBACK
= BUILDING STATIC PRESSURE (0-5 VDC)

= GROUND FOR ANALOG INPUTS
= GROUND FOR ANALOG INPUTS

I

Advertising