System installation, Networked multiple loop, Vcm-x component & systems wiring 19 – Orion System VCM-X E-BUS Component User Manual

Page 19

Advertising
background image

VCM-X Component & Systems Wiring

19

System Installation

6 VA minimum power and should be connected using 18
gauge minimum wire. In the Settings Menu, enter <63>
for the System Manager Address.

7. The Modular Service Tool SD will connect to any of the

controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller
is located near the communications connector. The
Communications setting must be set to Lo Speed
Network Mode.

8. Using 2 conductor shielded cable, connect from the

CommLink 5’s 3 wire communications connector to one
of the MiniLink PD’s 3 wire communications connector
marked “Network Loop”. The Loop switch on the back
of the CommLink 5 must be set to “Multiple”. The
CommLink only needs to be connected to one of the
MiniLink PDs on the system.

9. Using a modular cable, connect from each MiniLink

PD’s modular connector marked “Network Loop” to
the next MiniLink PD’s “Network Loop” modular
input connector using modular cable. Connect all the
remaining MiniLink PD’s in the same manner using a
daisy chain format.

10. Before powering up the controllers, set each VAV/

Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59. Set MiniLink PD’s address from 1 to
60.

Loops Containing VCM-X E-BUS Controllers without VAV/
Zone Controllers

1. Connect all VCM-X E-BUS Controllers on the loop in

a daisy chain format using 18 gauge minimum,

2 conductor shielded cable for communications.

Install a separate 24 VAC, 8 VA minimum, transformer

for each controller and wire to its transformer using 18

gauge minimum, 2 wire cable for power. Observe

polarity on all boards.

2. Connect 2 conductor shielded cable from one of the

controller’s 3 wire communications connector to the

MiniLink PD’s 3 wire communications connector

marked “Local Loop”. Use 18 gauge wire for power and

observe polarity on all boards.

3. Connect 2 wire shielded cable from the CommLink 5’s

3 wire communications connector to the MiniLink PD’s

3 wire communications connector marked “Network

Loop”. The Loop switch on the back of the CommLink

5 must be set to “Multiple”. Use the 110 VAC/24 VAC

power supply furnished with the CommLink for its

power

source.

4. Only one MiniLink PD on the system should connect to

the CommLink. Install a separate 24 VAC, 8 VA

minimum, transformer for each MiniLink PD and wire

to transformer using 18 gauge minimum, 2 wire cable

for power. Observe polarity on all boards. Each

MiniLink PD’s address switch should be set with a

unique address between 1 and 60.

5. Using a modular cable, connect from the each MiniLink

PD’s modular connector marked “Network Loop” to the

next MiniLink PD’s “Network Loop” modular input

connector using modular cable. Connect all the

remaining MiniLink PD’s in the same manner using a

daisy chain format.

6. The Modular Service Tool will connect to any of the

controllers using the supplied cable with DIN connectors

on both ends. The connection point on the controllers is

located near the communications connector. The

Communications setting must be set to Lo Speed

Network

Mode.

7.. The Modular System Manager is supplied with a 12

foot modular cable with a modular connector on one end

and stripped wires on the other. If the Modular System

Manager is to be mounted in remote location, run 18

gauge, 2 conductor shielded cable for communications

from one controller’s 3 wire terminal connector to one of

the MiniLink PD’s in the same manner using a daisy

chain format. The Communications setting must be set

to Lo Speed Network Mode.

8. The System Manager TS II utilizes a 3 wire

communication terminal block for connection to

any controller on the communications local loop that

has communication wire terminals. A separate

transformer is required for the System Manager TS II.

It has a 2 wire 24 VAC terminal block for connection to

a 24 VAC transformer. The transformer should be sized

to provide 6 VA minimum power and should be

connected using 18 gauge minimum wire. In the

Settings

Menu,

enter <63> for the System Manager

Address.

9. Address the VCM-X E-BUS Controllers from 1 to 59.

Networked Multiple Loop