Module wiring & connections, Hp1c module wiring when used with the vcm-x e-bus, Vcm-x component & systems wiring 98 – Orion System VCM-X E-BUS Component User Manual

Page 98: When used with orion vcm-x e-bus controller, Aaon one condenser head pressure wiring 1, Head pressure transducers

Advertising
background image

Module Wiring & Connections

VCM-X Component & Systems Wiring

98

HP1C Module Wiring When Used With The VCM-X E-BUS

FILENAME

DATE:

S. Olson

DESCRIPTION:

PAGE

DRAWN BY:

When Used With Orion VCM-X E-BUS Controller

JOB NAME

06/04/15

HP1C-1A.CDR

AAON One Condenser Head Pressure Wiring

1

Wiring For One Condenser Head Pressure Module
When Used With Orion VCM-X E-BUS Controller

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure

Transducers

OE370-23-HP1C

One Condenser

Head Pressure Module

OPTIONS Dip Switch Setting

Not Required When

Connected To

VCM-X Modular E-BUS or

VCM-X WSHP E-BUS

Controller

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

COM

+

Condenser

Signal A

Connect To Other

WattMaster-Approved

E-BUS Expansion

Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe
Polarity! All boards
must be wired with
GND-to-GND and 24
VAC-to-24 VAC.

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

ALL RELAY OUTPUTS

ARE

COMM

HSSC Cable

Connect To VCM-X E-BUS

Controller or VCM-X WSHP E-BUS

Controller

Set ADDRESS Dip

Switch 1 to ON for

Water Cooled or to OFF

for Air Cooled.

Currently showing OFF

for Air Cooled.

Set ADDRESS Dip

Switch 2 to OFF on all

communicating

applications unless it is

intended to be the

Second Head Pressure

Module on a system. If

set to ON, it will not

communicate. Currently

showing OFF.

Set ADDRESS Dip
Switch 4 to OFF to

make reversing valve

"ON to Heat / OFF to

Cool” Set to ON to

make reversing valve

“ON to Cool / OFF to

Heat. Currently

showing OFF.

ADDRESS

BIN 1

BIN 2

BIN 3

COM

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102057-A

Rev.: 1J

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VA

C

GND

HEAD
PRESSURE
TRANSDUCER #1/

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

PWM2+

One Condenser Head Pressure Module

1C

Orion No.:OE370-23-HP

AAON No.:

R74860

AO1

AO2

GND

COND. SIGNAL

NOT USED

PWM1-

PWM1+

PWM2-

COND. FAN

NOT USED

COND. FAN

NOT USED

GND

RELA

Y

CONT

ACT

RA

TING IS 1

AMP

MAX @ 24 V

AC

COND. ENABLE

NOT USED

NOT USED

R1

R2

R3

R4

RC

RELAY COMMON

BIN 1

BIN 2

BIN 3

COM

NOT USED
COMMON

COND. ENABLE INPUT
REV. VLV. INPUT ENABLE

A1

A2

A3

A4

REV. VLV. ENABLE

www.aaon.com

R2

REVERSING VALVE A ENABLE

+24 Volts

Duty Cycle

YELLOW

BLUE +24 OUT

Condenser Fan

ECM Motor

Figure 74: OE370-23-HP1C One Condenser Head Pressure Module to VCM-X E-BUS Controller Wiring