VCM-X Component & Systems Wiring

109

Miscellaneous Diagrams and Technical Information

Figure 85: OE334-26-WSHP-X2 WSHP-X2 Controller Dual Circuit Wiring to VCM-X E-BUS Controller

WSHP-X2 Controller Wiring When Used With The VCM-X E-BUS

FILENAME

DATE:

S. Olson

DESCRIPTION:

PAGE

DRAWN BY:

When Used With Orion VCM-X E-BUS Controller

JOB NAME

06/05/15

WSHPX2-Wr1-2.CDR

AAON WSHP-X2 Wiring - Dual Circuit

2

Wiring For WSHP-X2 When Used With Orion VCM-X E-BUS Controller

Connect To Other

WattMaster-Approved

E-BUS Expansion

Module(s)

WARNING!! Observe
Polarity! All boards must
be wired with GND-to-
GND and 24 VAC-to-24
VAC. Failure to observe
polarity could result in
damage to the boards.

HSSC Cable

WATTMASTER CONTROLS

Y 102374 REV 0

S

MADE IN USA

OE334-26-WSHP-X2

Water Source

Heat Pump X2 Module

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R4
R5

R3

R2

COMM

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

HVAC

24 VAC

GND

T1

WATER POF A

BIN6

COM

E

LEAVING WATER
TEMPERATURE
FOR SYSTEM A

T2

BIN7

WATER POF B

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

CIRCUIT A1
SUCTION PRESSURE
TRANSDUCER

SIG 2

GND

+V

BK

RD
WH

SIG 1

GND

+V

BK

RD
WH

CIRCUIT A2
SUCTION PRESSURE
TRANSDUCER

CIRCUIT B1
SUCTION PRESSURE
TRANSDUCER

CIRCUIT B2
SUCTION PRESSURE
TRANSDUCER

AOUT1
AOUT2
AOUT3
AOUT4

COMP A1
COMP A2
COMP B1

COMP B2

SEE
NOTE
BELOW

NOTE:
DIGITAL COMPRESSORS = 1.5-5VDC

VFD COMPRESSORS = 0-10VDC

WattMaster Label

#S

000063

Rev.: 1B

W

E-BUS

HSSC

CONNECT

M

ENTER

UP

DOWN

ALARM

MENU

OE334-26-WSHP-X2 WSHP-X2 MODULE

AAON NO.: V48820

+24 V

A

C

GND

www.orioncontrols.com

www.aaon.com

- COMP A1 EN

- HEAT ENABLE

- COMP A2 EN

- H2O POF A

- COMP B1 EN

- H2O POF B

- COMP B2 EN

- COMMON

GND

- LEAVING WATER TEMP

- GROUND

- LEAVING WATER TEMP

AOUT1

- COMP A1

DIGITAL/VFD COMPRESSORS

A1, A2, B1, B2

RELAY CONTACT RATING

IS 1 AMP MAX @ 24 VAC

COMP. A2 ENABLE

COMP. A1 ENABLE

R1

R2

R3

R4

R5

RC

RELAY COMMON

COMP. B1 ENABLE

COMP. B2 ENABLE

ALARM OUTPUT

CONNECT TO
CNTLR C2
TERM.

+5V

PRES

GND

+5V

PRES

GND

SUCT. PR. SENSOR
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

NOT USED
PRES 1=A1, PRES 2=A2
PRES 3=B1, PRES 4=B2

+5 NOT USED, PRES TO P6 & GND TO P5

+5 TO RED, PRES TO WHT & GND TO BLK

DIGITAL COMRESSORS

NON-DIGITAL COMPRESSORS

AOUT2

- COMP A2

AOUT3

- COMP B1

AOUT4

- COMP B2

E-BUS

HSSC

CONNECT

BIN1

BIN2

BIN3

BIN4

BIN5

BIN6

BIN7

COM

T 1

T 2

LEAVING WATER
TEMPERATURE
FOR SYSTEM B

Connect To Other

WattMaster-Approved

E-BUS Expansion

Module(s)

Connect To

VCM-X E-BUS