VCM-X Component & Systems Wiring

110

Miscellaneous Diagrams and Technical Information

Figure 86: OE377-26-00061 PREHEAT-X Controller Single Circuit Wiring to VCM-X E-BUS Controller

M

ENTER

UP

DOWN

ALARM

MENU

ALARM CONTACT

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

HEAT 6

RLY COMM

HEAT

OUTPUTS

ANALOG

OUTPUTS

0-10V MOD. SCR

GND

PWM +

PWM -

OE377-26-00061 PREHEAT-X

AAON No.: V48510

WattMaster Label

#LB102XXX-A

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

LAT1

0-10V RESET

LAT2

OAT

GND

GND

ANALOG INPUTS

BINARY INPUTS

RS-485 COMM

+24

V

AC

GND

www.orioncontrols.com

www.aaon.com

ENABLE

T(-)

EMERG. SHUTDOWN

SHLD

FUTURE USE

R(+)

CONTACT RATING IS

1 AMP MAX

@ 24 VAC

AIN1

Entering Air Temperature

Sensor

Reset In

0-10 VDC

GND

+

-

Emergency

Shutdown

Line

GND

24V

AC

40 VA

Transformer

Minimum

Heat 1 Relay

Heat 2 Relay

Heat 3 Relay

Heat 4 Relay

Heat 5 Relay

Heat 6 Relay

COM

Alarm

Note:
All Relay Outputs Are
Normally Open And Rated
For 24 VAC Power Only.
1 Amp Maximum Load.

Relay
Contact

PWM SSR

+

Modulating SCR

(0-10 VDC)

+

PREHEAT-X CONTROLLER

(OE377-26-00061)

AIN2
AIN3

RST

GND
GND

BIN1
BIN2

Leaving Air 2

Temperature Sensor

Leaving Air 1

Temperature Sensor

SAFETIES

(BY OTHERS)

N.C.

Heat Enable

Signal (24 VAC)

W1

NOTE: Reset In And Heat

Enable Inputs Are Used In

Stand-Alone Mode Only

Mount Inside PREHEAT-X

Box Wall

Make Splice

Connections

Inside Sensor Enclosure

As Shown. Seal All

Conduit Fittings With

Silicone Sealant

Mount Sensor Outdoors

In Shaded Protected

Area & In Upright

Position As Shown

Mount Inside PREHEAT-X

Box Wall

M

ENTER

UP

DOWN

ALARM

MENU

ALARM CONTACT

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

HEAT 6

RLY COMM

HEAT

OUTPUTS

ANALOG

OUTPUTS

0-10V MOD. SCR

GND

PWM +

PWM -

OE377-26-00061 PREHEAT-X

AAON No.: V48510

WattMaster Label

Rev.: 1D

#S

000062

W

E-BUS

CONNECT

E-BUS

CONNECT

LAT1

0-10V RESET

LAT2

EAT

GND

GND

ANALOG INPUTS

BINARY INPUTS

RS-485 COMM

+24 V

A

C

GND

www.aaon.com

ENABLE

T(-)

EMERG. SHUTDOWN

SHLD

FUTURE USE

R(+)

CONTACT RATING IS

1 AMP MAX

@ 24 VAC

www.orioncontrols.com

MSTP

BACnet

HSSC E-BUS Cable

Connects To

VCM-X Controller’s

Expansion Port

FILENAME

DATE:

S. Olson

DESCRIPTION:

PAGE

DRAWN BY:

When Used With Orion VCM-X E-BUS Controller

JOB NAME

06/10/15

PREHEATX-1A.CDR

AAON PREHEAT-X Wiring

1

Wiring For PREHEAT-X When Used With Orion VCM-X E-BUS Controller

PREHEAT-X Controller Wiring When Used With The VCM-X E-BUS