Module wiring & connections, Vcm-x component & systems wiring, When used with orion vcm-x e-bus controller – Orion System VCM-X E-BUS Component User Manual

Page 99: Head pressure transducers, Hssc cable connect to vcm-x e-bus, Filename date: s. olson description: page drawn by

Advertising
background image

VCM-X Component & Systems Wiring

Module Wiring & Connections

99

HP2C2 Controller Wiring When Used With The VCM-X E-BUS

Figure 75: OE370-23-HP2C2 Two Condenser Head Pressure Module to VCM-X E-BUS Controller Wiring

FILENAME

DATE:

S. Olson

DESCRIPTION:

PAGE

DRAWN BY:

When Used With Orion VCM-X E-BUS Controller

JOB NAME

06/05/15

HP2C2-1A.CDR

Two Condenser Head Pressure Module Wiring

1

Wiring For Two Condenser Head Pressure Module When Used With Orion VCM-X E-BUS Controller

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure

Transducers

OE370-23-HP2C2

Two Condenser

Head Pressure II Module

OPTIONS Dip Switch Setting

Not Required When Connected

To VCM-X E-BUS

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

Connect To Other

WattMaster-Approved

E-BUS Expansion

Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe
Polarity! All boards must
be wired with GND-to-
GND and 24 VAC-to-24
VAC.

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

ALL RELAY OUTPUTS

ARE

HSSC Cable

Connect To

VCM-X E-BUS

Set ADDRESS Dip Switch 1 to ON for Water

Cooled or to OFF for Air Cooled. Currently

showing OFF for Air Cooled.

Set ADDRESS Dip Switch 2 to OFF on all

communicating applications unless it is

intended to be the Second Head Pressure

Module on a system. If set to ON, it will not

communicate. Currently showing OFF.

Set ADDRESS Dip Switch 3 to ON to

disable Circuit B alarms when only one

Condenser is Used. Currently showing OFF.

Set ADDRESS Dip Switch 4 to OFF to make

reversing valve "ON to Heat / OFF to Cool.”

Set to ON to make reversing valve “ON to

Cool / OFF to Heat.” Currently showing OFF.

ADDRESS

BIN 1

BIN 2

BIN 3

COM

+24 Volts

Condenser Fan A

ECM Motor

Duty Cycle

Condenser Fan B

ECM Motor

COM

+

Condenser

Signal B

COM

+

Condenser

Signal A

CONDENSER A ENABLE

R1

R3

CONDENSER B ENABLE

COMM

REVERSING VALVE B ENABLE

REVERSING VALVE A ENABLE

R4

R2

YELLOW

BLUE +24 OUT

+24 Volts

Duty Cycle

YELLOW

BLUE +24 OUT

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102110-A

Rev.: 1A

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VAC

GND

BIN 1

BIN 2

BIN 3

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

REV. VLV. ENABLE INPUT

COMMON

PWM2+

AAON No.:

V20660

AO1

AO2

GND

COND. A ENABLE INPUT

COND. B ENABLE INPUT

COND. A SIGNAL
COND. B SIGNAL

PWM1-

PWM1+

PWM2-

COND. FAN A

COND. FAN B

COND. FAN A

COND. FAN B

GND

Two Condenser Head Pressure II Module

2C2

Orion No.:OE370-23-HP

www.aaon.com

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

COND. A ENABLE

COND. B ENABLE

REV. VLV. A ENABLE

REV. VLV. B ENABLE

R1

R2

R3

R4

RC

RELAY COMMON

A1

A2

B1

B2

Advertising