VCM-X Component & Systems Wiring

76

Communication Devices

24 VAC Power

If Desired A 24 VAC Transformer

Rated At 12 VA Minimum May Be

Used Instead Of The Supplied Power Pack.
Use 18 Gauge Minimum 2 Conductor Wire
Between The Transformer & CommLink 5
Terminals

(Not

Included)

120 to 24 VAC Power Pack
(Included) Connect To 120/1/60
Duplex Receptacle (By Others)

USB Cable (Included).
Connect This Cable To
Your Computer USB Port
For Direct Connection To
The CommLink 5.

CommLink 5

Communications Interface

NOTES:

1) For Direct Connection Via USB, Your Computer Must Have An Unused USB
Port Available. Drivers For Your USB Port Are Provided On A CD Supplied With
The CommLink 5. Please Follow The Directions In The CommLink 5 Technical
Guide To Install And Configure The USB Drivers.

2) The CommLink 5 Cannot Communicate With The Control System Through Its
Ethernet Port And USB Port At The Same Time.

3) All Wiring Must Conform To Applicable Federal, State & Local Electrical Wiring
Codes.

18 Gauge 2 Conductor
With Shield (Not Included)
See Note 1

Connect To Controller
As Required By Your
Specific System
Wiring Instructions.

Serial #

COMPUTER

USB

10/100

ETHERNET

DIAG

485 LOOP POWER

ACT

LNK

Optional Items
Not Required
For CommLink-Only
Installations.

When Used With
MiniLink, Switch
Should Be Set To
Multiple.

HIGH

LOW

BAUD

R(

+

)

24V

GND

SH

LD

T(

-)

MUL

T

IPLE

SINGLE

LOOP

WARNING! If You Are Using The IP
Module With Your CommLink, Do Not
Have Your Ethernet Connection And
USB Connection Connected At The
Same Time. This Could Cause
Unreliable Communications.

Optional - Prefabricated

Ft. Long CAT5

Ethernet Cable (Included With Optional OE415-
02 IP Module Kit).

If A Longer

Ethernet Cable Is Required, You Will Need To
Obtain (From Others) And Install An Ethernet
Cable Of The Required Length For Your
Installation.

10

Connect To A 10/100 Base-T

Ethernet Router On Your LAN.

NOTE: A CommLink Is Always Required With A Networked Multiple Loop System.

Computer Connection, or Direct Computer

System Is Desired. An IP Module Is Only Required If E-Mail Alarm

Notification Or Remote Computer Connection Is Required.

It Is Used For Alarm Callout, Remote
Connection To The

FILENAME

DESCRIPTION:

PAGE

Wiring & Connection Diagram

JOB NAME

1 of 1

CommLink5-Setup1A.cdr

OE361-13 CommLink 5

BY: B. Crews, S. Olson

DATE: 01/18/13

Figure 54: OE361-13 CommLink 5 Computer Connection and Wiring