VCM-X Component & Systems Wiring

83

Communication Devices

Power/Comm Board Wiring For Local Loops

Figure 61: OE365-01 Power/Comm Board Wiring When Used For Local Loop Devices

Notes:

1.) All wiring to be in accordance with local and national electrical codes

and specifications.

2.) All modular power/comm cables are to be WattMaster part number

PCC-xx or PCCE-xx cables. All other communication wiring to be 2
conductor twisted pair with shield (Belden #82760 or equivalent).

Power/Comm Cable

Power/Comm Board,

System Manager, Or Modular VAV/Zone Controller On Local Loop
If This Is The First Power/Comm Board On The Local Loop,
No Connection Is Required. See Note 2.

From Other

Power/Comm Cable To

Power/Comm

System Manager, Or Modular VAV/Zone Controllers On Local Loop Only.

Other

Board(s),

Connect To Modular VAV/Zone Controller
If This Is First Power/Comm Board
On Local Loop - Otherwise No
Connection Is Required. See Note 2.

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

Local Loop Wiring Diagram

JOB NAME

02/11/2004

O-Pwr-CommWire1A.CDR

OE365-01 Orion Power/Comm Board

1 of 2

TB2

VA
C

F1

25

4A

24

SHLD

T

R

POWER

LD1

TB1

C1

POWER & COMM

DIST

. BOARD

YS101856

REV

. 0

P5

P4

P3

P1

D1

V1

R1

P2

COMMPIN

POWER & COMM

OUT

Line Voltage

24VAC

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring Is

Straight Thru

Local Loop RS-485

9600 Baud

Local Loop RS-485

9600 Baud

24VAC Transformer (By Others)
See System Configuration Installation &
Commissioning Section Of This Manual
For Detailed Sizing Information

4 Amp Slow Blow Fuse

WARNING!

DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!

Note:
Diagram Shown Is For Wiring Of
Power/Comm Board When Used
For Connecting Local Loop Devices
Such As Modular VAV/Zone
Controllers, System Manager(s) and
Other Power/Comm Boards. See
Page 2 Of This Drawing For Wiring
When Power/Comm Board Is Used
For Connection Of MiniLink Polling
Devices On The Network Loop.

CAUTION!

No

Can Be

Connected To The Same
Power/Comm Board(s) That
Are Used To Supply Power
And Communications For
Modular VAV/Zone
Controllers And System
Manager On The Local Loop.

MinLink PDs