Vcm-x expansion module wiring, Airflow monitoring station, Vcm-x component & systems wiring – Orion System VCM-X E-BUS Component User Manual

Page 57: Gtc116 series, greentrol, Ga-200-n series, and paragon microtrans, Vcm-x e-bus controller

Advertising
background image

VCM-X Component & Systems Wiring

VCM-X Expansion Module Wiring

57

Airflow Monitoring Station

Figure 38: OE365-15-EBA - EBTRON

®

GTC116 Series, GreenTrol

TM

GA-200-N Series, and Paragon

MicroTrans

EQ

Series Air Flow Measurement Digital Transmitter Wiring

COMM

COMM

NET-

NET-

NET+

NET+

Airflow Measurement

Digital Transmitter Terminals

For Outdoor Air CFM

(Set Address Switch To 9)

Airflow Measurement

Digital Transmitter Terminals

For Return Air CFM

(Set Address Switch To 10)

Airflow Measurement

Digital Transmitter Terminals

For Supply Air CFM

(Set Address Switch To 11)

COMM

NET-

NET+

VCM-X E-BUS Controller

OE365-15-EBA

E-BUS Adapter Board

HSSC Cable Connect To

VCM-X E-BUS Port

I2C DIGITAL

SENSOR

I2C

EXPANSION

STATIC

PRESSURE

ANALOG INPUT JUMPER SETTINGS
MUST BE SET AS SHOWN FOR
PROPER OPERATION

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

AI2

AI3

AI4

THERM

THERM

THERM

THERM

4-20mA

4-20mA

4-20mA

4-20mA

4-20mA

0-10V

0-10V

0-10V

0-10V

0-10V

0-5V

0-5V

0-5V

0-5V

0-5V

AI5

AI7

WattMaster Label

#LB102033-01

AI1 AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

EMERGENCY SHUTDOWN

AI1 SET

AI1

THERM

THERM

4-20mA
0-10V

0-5V

ANALOG INPU

JUMPER

SETTINGS

HSSC Cable Connect To

VCM-X E-BUS Port

Connect To

VCM-X E-BUS Port

FILENAME

DATE:

S. Olson

DESCRIPTION:

PAGE

BY:

JOB NAME

OVCMX-Airflow-Station-1A.cdr

1 of 1

05/15/15

VCM-X Expansion Module

Airflow Monitoring Station Wiring

Advertising