VCM-X Component & Systems Wiring

125

Miscellaneous Diagrams and Technical Information

OE271 Pressure Sensor Testing Instructions

Use the voltage column to check the Duct Static Pressure Sensor
while connected to powered controllers. Read voltage with meter
set on DC volts. Place the “-” (minus) lead on the GND terminal and
the “+” (plus) lead on the 0-5 pin terminal on (TP) with the jumper
removed. Be sure to replace the jumper after checking.

OE258-01 Building Pressure Sensor Testing
Instructions

Use the voltage column to check the Building Static Pressure Sensor
while connected to a powered expansion board. Read voltage with
meter set on DC volts. Place the “-”(minus) lead on terminal labeled
GND and the “+” lead on terminal AIN4 on the Analog Input/Output
Expansion Board.

Pressure Sensors Voltage-Resistance Tables

OE271 Duct Static Pressure Sensor
This sensor is used to sense duct static pressure for the Orion system
controllers. The OE271 sensor is a 0-5” W.C. pressure range, 0-5
VDC voltage range sensor. Use the table and testing information
below to check for proper sensor operation.

OE258-01 Building Pressure Sensor
This sensor is used to sense building pressure for the Orion system
controllers. The OE258-01 sensor is a -0.25” to +0.25” W.C. pres-
sure range, 0-5 VDC voltage range sensor. Use the table and testing
information below to check for proper sensor operation.

OE271 Duct Static Pressure Sensor

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

0.00

0.25

2.60

2.33

0.10

0.33

2.70

2.41

0.20

0.41

2.80

2.49

0.30

0.49

2.90

2.57

0.40

0.57

3.00

2.65

0.50

0.65

3.10

2.73

0.60

0.73

3.20

2.81

0.70

0.81

3.30

2.89

0.80

0.89

3.40

2.97

0.90

0.97

3.50

3.05

1.00

1.05

3.60

3.13

1.10

1.13

3.70

3.21

1.20

1.21

3.80

3.29

1.30

1.29

3.90

3.37

1.40

1.37

4.00

3.45

1.50

1.45

4.10

3.53

1.60

1.53

4.20

3.61

1.70

1.61

4.30

3.69

1.80

1.69

4.40

3.77

1.90

1.77

4.50

3.85

2.00

1.85

4.60

3.93

2.10

1.93

4.70

4.01

2.20

2.01

4.80

4.09

2.30

2.09

4.90

4.17

2.40

2.17

5.00

4.25

2.50

2.25

OE258 Building Pressure Sensor

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

Pressure

@

Sensor

(“ W.C.)

Voltage

@

Input

(VDC)

-0.25

0.00

0.01

2.60

-0.24

0.10

0.02

2.70

-0.23

0.20

0.03

2.80

-0.22

0.30

0.04

2.90

-0.21

0.40

0.05

3.00

-0.20

0.50

0.06

3.10

-0.19

0.60

0.07

3.20

-0.18

0.70

0.08

3.30

-0.17

0.80

0.09

3.40

-0.16

0.90

0.10

3.50

-0.15

1.00

0.11

3.60

-0.14

1.10

0.12

3.70

-0.13

1.20

0.13

3.80

-0.12

1.30

0.14

3.90

-0.11

1.40

0.15

4.00

-0.10

1.50

0.16

4.10

-0.09

1.60

0.17

4.20

-0.08

1.70

0.18

4.30

-0.07

1.80

0.19

4.40

-0.06

1.90

0.20

4.50

-0.05

2.00

0.21

4.60

-0.04

2.10

0.22

4.70

-0.03

2.20

0.23

4.80

-0.02

2.30

0.24

4.90

-0.01

2.40

0.25

5.00

0.00

2.50

Advertising