Communication devices, Vcm-x component & systems wiring 84, Warning – Orion System VCM-X E-BUS Component User Manual

Page 84: Caution

Advertising
background image

VCM-X Component & Systems Wiring

84

Communication Devices

Notes:

1.) All wiring to be in accordance with local and national electrical codes

and specifications.

2.) All modular power/comm cables are to be WattMaster part number

PCC-xx or PCCE-xx cables. All other communication wiring to be 2
conductor twisted pair with shield (Belden #82760 or equivalent).

Comm/Power Cable

Power/Comm

Board Used For Connecting MiniLink PDs Or Previous MiniLink
PD On Network Loop. If This Is The First Power/Comm Board
On The Network Loop, This Power/Comm Cable Connection Is
Not Required. Instead Use The 3 Pole Terminal Block
Communication Connection As Shown Below And Connect
To The CommLink. See Note 2.

From Other

Connect Power/Comm Cables To

Power/Comm

Or MiniLink PDs On The Network Loop Only.

Other

Distribution Board

Use To Connect CommLink When
This Is the First Power/Comm Board
On The Network Loop. Otherwise No
Connection Is Required. See Note 2.

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

Network Wiring Diagram

JOB NAME

O-Pwr-CommWire1A.CDR

OE365-01 Orion Power/Comm Board

2 of 2

TB2

VA
C

F1

25

4A

24

SHLD

T

R

POWER

LD1

TB1

C1

POWER & COMM

DIST

. BOARD

YS101856

REV

. 0

P5

P4

P3

P1

D1

V1

R1

P2

COMMPIN

POWER & COMM

OUT

Line Voltage

24VAC

R

SH

T

R

SH

T

R

SH

T

R

SH

T

All Comm Loop Wiring Is

Straight Thru

Network Loop RS-485

192000 Baud

Network Loop RS-485

19200 Baud

4 Amp Slow Blow Fuse

WARNING!

DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!

CAUTION!

No Local Loop Devices
(Modular VAV/Zone
Controllers, System
Manager(s) Etc.) Can Be
Connected To The Same
Power/Comm Board(s) That
Are Used To Supply Power
And Communications For
MinLink PDs On The
Network Loop.

Note:
Diagram Shown Is For Wiring

For Wiring Of Local Loop Devices
Such As Modular VAV/Zone
Controllers, System Manager(s) and
Other Power/Comm Boards On The
Local Loop See Page 1 Of This
Drawing For Wiring .

When

Power/Comm Board Is Used For
Connection Of MiniLink Polling
Devices On The Network Loop.

02/11/2004

24VAC Transformer (By Others)
See System Configuration Installation &
Commissioning Section Of This Manual
For Detailed Sizing Information

Power/Comm Board Wiring - When Used For Network Loop Devices

Figure 62: OE365-01 Power/Comm Board Wiring When Used For Network Loop Devices