Scanner instruction manual, Serial communications, General – Precision Digital PD6080 User Manual

Page 11

Advertising
background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

11

Serial Communications

SCANNER ID

1 – 247 (Scanner Modbus address)

BAUD RATE

300 – 19,200 bps

TRANSMIT
TIME DELAY

Programmable 0 to 4999 ms
This is the time the scanner will wait for a slave to respond before sending
another request on the bus. This value should be greater than 100 ms to avoid
collisions on the bus.

DATA

8 bits (1 start bit, 1 or 2 stop bits)

PARITY

Even, Odd, or None with 1 or 2 stop bits

BYTE-TO-BYTE
TIMEOUT

0.01 – 2.54 second

TURN AROUND
DELAY

Less than 2 ms (fixed)

Note: Refer to the P

RO

V

U

®

Scanner Modbus Register Tables located at www.predig.com.

General

INPUT/OUTPUT

Modbus RTU over RS-485, Two analog inputs (4-20 mA,

±10 V)

DISPLAY

Upper display: 0.60" (15 mm) high, red LEDs
Lower display: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking

DISPLAY
INTENSITY

Eight user selectable intensity levels

OVERRANGE

Values greater than 999999 cause the display to flash 999999

UNDERRANGE

Values less than -99999 cause the display to flash -99999

PROGRAMMING
METHODS

Four front panel buttons, digital inputs, PC and ScanView software, Modbus
registers, or cloning using Copy function.

MAX/MIN
DISPLAY

Max/min readings are stored until reset by the user or when power to the
scanner is turned off. User can reset by front panel pushbuttons, digital input, or
via Modbus registers.

PASSWORD

Three programmable passwords restrict modification of programmed settings.

Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.

F4 DIGITAL INPUT
CONTACTS

50k ohm pull-up to 3.3 VDC.
Connect normally open contacts across F4 to COM.

F4 DIGITAL INPUT
LOGIC LEVELS

Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC

NON-VOLATILE
MEMORY

All programmed settings are stored in non-volatile memory for a minimum of
ten years, with or without power.

POWER
OPTIONS

85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC

± 10%, 15 W max

FUSE

Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 scanners
may share one 5 A fuse

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals P+ & P- : 24 VDC

± 10%.

Selectable for 24, 10, or 5 VDC supply (internal jumper J4).
ProVu Series (PD6080/81): 85-265 VAC models rated @ 200 mA max, 12/24 VDC
powered models rated @ 100 mA max, 5 or 10 VDC supply rated @ 50 mA max.
ProtEX-MAX (PD8 Series): All models transmitter supply rated @ 25 mA max.