PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

14

CALIBRATION
RANGE

Input
Range

Minimum Span
Input 1 & Input 2

4-20 mA

0.15 mA

±10 V

0.10 V

An error message will appear if the input 1 & input 2 signals are too close together.

INPUT
IMPEDANCE

Voltage ranges: greater than 500 k

Ω

Current ranges: 50 - 100

Ω (depending on resettable fuse impedance)

INPUT
OVERLOAD

Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.