Scanner instruction manual, Relay operation details – Precision Digital PD6080 User Manual

Page 60

Advertising
background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

60

Relay Operation Details

Overview

The relay capabilities of the scanner expand its usefulness beyond simple indication to provide users with
alarm and control functions. These capabilities include front panel alarm status LEDs, as well as either 2
or 4 optional internal relays, and/or 4 external relays via expansion modules. Typical applications include
high or low temperature, level, pressure or flow alarms, control applications such as simple on/off pump
control, and pump alternation control for up to 8 pumps. There are four basic ways the relays can be
used:
1. High or Low Alarms with Latching or Non-Latching Relays
2. Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Pump Alternation Control for up to 8 Pumps

Relays Auto Initialization

When power is applied to the scanner, the front panel LEDs and alarm relays will reflect the state of the
input to the scanner after the first response from the slave device. The following table indicates how the
alarm LEDs and relays will react on power-up based on the set and reset points:

Alarm #

HI or LO

Alarm

Set Point

Reset

Point

Power-Up

Reading

Relay &

LED

1 HI 1000

500 499 Off

2 LO 700 900 499 On

3 LO 250 400 499 Off

4 HI 450 200 499 On


Fail-Safe Operation (failsf)

The following table indicates how the relays behave based on the fail-safe selection for each relay:

Fail-Safe
Selection

Non-Alarm State

Alarm State

Power Failure

NO NC

NO

NC

Off

Open

Closed

Closed

Open

Relays go to non-alarm
state

On

Closed

Open

Open

Closed

Relays go to alarm
state

Note: NO = Normally Open, NC = Normally Closed. This refers to the condition of the relay contacts when

the power to the scanner is off.