Scanner instruction manual, Isolated 4-20 ma transmitter output, Dual process input – Precision Digital PD6080 User Manual

Page 13

Advertising
background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

13

TIME DELAY

0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay

FAIL-SAFE
OPERATION

Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.

In case of power failure, relay will go to alarm state.

AUTO
INITIALIZATION

When power is applied to the scanner, relays will reflect the state of the input to
the scanner.

Isolated 4-20 mA Transmitter Output

OUTPUT SOURCE

PV1-16, math channels C1-4, set points 1-8, or manual control mode

SCALING RANGE

1.000 to 23.000 mA for any display range

CALIBRATION

Factory calibrated: 4.000 to 20.000 = 4-20 mA output

ANALOG OUT
PROGRAMMING

23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break

COMMUNICATIONS
BREAK

Programmable mA output when a slave device does not reply within the
response timeout.

ACCURACY

± 0.1% of span ± 0.004 mA

TEMPERATURE
DRIFT

0.4 µA/

°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient.

Note: Analog output drift is separate from input drift.

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals I+ & R: 24 VDC

± 10%. May be used to power the 4-20 mA output or

other devices. Refer to Figure 6 on page 19 and Figure 13 on page 23.
ProVu Series (PD6080/6081): All models rated @ 40 mA max.
ProtEX-MAX (PD8 Series): All models @ 25 mA max.

EXTERNAL LOOP
POWER SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

Ω

700

Ω

35 VDC (external)

100

Ω

1200

Ω

Dual Process Input

TWO INPUTS

Two analog inputs, each separately field selectable:
0-20 mA, 4-20 mA;

±10 V (0-5, 1-5, 0-10 V)

PV ANALOG
CHANNEL ID

Ch-A mA: Assign PV to ID 256 or Ch-A volt: 257;
Ch-B mA: Assign PV to ID 258 or Ch-B volt: 259

ACCURACY

±0.03% of calibrated span ±1 count, square root & programmable exponent
accuracy range: 10-100% of calibrated span

TEMPERATURE
DRIFT

0.005% of calibrated span/

°C max from 0 to 65°C ambient,

0.01% of calibrated span/

°C max from -40 to 0°C ambient

SIGNAL INPUT
CONDITIONING

Linear, square root, programmable exponent, or
round horizontal tank volume calculation

MULTI-POINT
LINEARIZATION

2 to 32 points for PV1 and PV2

PROGRAMMABLE
EXPONENT

1.0001 to 2.9999

LOW-FLOW
CUTOFF

0-999999 (0 disables cutoff function) for PV1 and PV2

Advertising