Scanner instruction manual – Precision Digital PD6080 User Manual

Page 80

Advertising
background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

80

Square Root Function Menu (Square)

The square root function is used to calculate flow measured with a differential pressure transmitter. The
flow rate is proportional to the square root of the differential pressure. Scale the scanner so that the low
input signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20 mA) is equal to the
maximum flow.

SAVED flashes

before moving

to next PV.


Advertising