PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

12

ISOLATION

4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply

OVERVOLTAGE
CATEGORY

Installation Overvoltage Category II: Local level with smaller transient
overvoltages than Installation Overvoltage Category III.

ENVIRONMENTAL

ProVu Series (PD6080/6081):
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
ProtEX-MAX (PD8 Series):
T6 Class operating temperature range Ta = -40 to 60°C
T5 Class operating temperature range Ta = -40 to 65°C
See LIM8 ProtEX-MAX instruction manual for additional details.

MAX POWER
DISSIPATION

ProtEX-MAX (PD8 Series): Maximum power dissipation limited to 15.1 W.
See LIM8 ProtEX-MAX instruction manual for additional details.

CONNECTIONS

Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external
relays, digital I/O, and serial communication adapters.

ENCLOSURE

1/8 DIN, high impact plastic, UL 94V-0, color: black

MOUNTING

1/8 DIN panel cutout required: 3.622” x 1.772” (92 mm x 45 mm)
Two panel mounting bracket assemblies are provided.

TIGHTENING TORQUE Screw terminal connectors: 5 lb-in (0.56 Nm)

OVERALL
DIMENSIONS

2.45" x 4.68" x 4.19" (62 mm x 119 mm x 106 mm) (H x W x D)

WEIGHT

9.5 oz (269 g)

WARRANTY

3 years parts and labor

Relays

RATING

2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @
30 VDC and 125/250 VAC resistive load; 1/14 HP (

≈ 50 W) @ 125/250 VAC for

inductive loads

NOISE
SUPPRESSION

Noise suppression is recommended for each relay contact switching inductive
loads.

ELECTRICAL NOISE
SUPPRESSION

A suppressor (snubber) should be connected to each relay contact switching
inductive loads to prevent disruption to the microprocessor’s operation.
Recommended suppressor value: 0.01 µF/470

Ω, 250 VAC (PDX6901).

DEADBAND

0-100% of span, user programmable

HIGH OR LOW ALARM User may program any alarm for high or low trip point.

Unused alarm LEDs and relays may be disabled (turn off).

RELAY
OPERATION

Automatic (non-latching)
Latching (requires manual acknowledge)
Sampling (based on time)
Pump alternation control (2 to 8 relays)
Off (disable unused relays and enable Interlock feature)
Manual on/off control mode

RELAY RESET

User selectable via front panel buttons, digital inputs, or PC

1. Automatic reset only (non-latching), when the input passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may be assigned to acknowledge relays

programmed for manual reset.