Scanner instruction manual – Precision Digital PD6080 User Manual

Page 62

Advertising
background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

62

Non-Latching Relay (A-man)

Automatic + manual reset at any time

Condition LED

Relay

Normal Off

Off

Alarm On

On

Normal Off

Off

Next Alarm

On

On

Ack

On

Off

Normal Off

Off


In this application, the scanner is set up for automatic and manual reset at any time (non-latching relay).
The LED and the relay automatically reset when the scanner returns to the normal condition.
The next time an alarm occurs, the operator acknowledges the alarm manually while the alarm condition
still exists. This causes the relay to reset, but the LED stays on until the scanner returns to the normal
condition.

Latching Relay (LatcH)

Manual reset any time

Condition LED

Relay

Normal Off

Off

Alarm On

On

Ack Off

Off


In this application, the scanner is set up for manual reset at any time. Acknowledging the alarm even if
the alarm condition is still present resets the relay and turns off the LED.

Latching Relay (Lt-Clr)

Manual reset only after alarm condition has cleared

Condition LED

Relay

Normal Off

Off

Alarm On

On

Ack (No effect)

On

On

Normal On

On

Ack Off

Off


In this application, the scanner is set up for manual reset only after the signal passes the reset point
(alarm condition has cleared). Acknowledging the alarm while it is still present has no effect on either the
LED or the relay. When the alarm is acknowledged after it returns to the normal state, the LED and the
relay go off. Notice that the LED remains on, even after the scanner returns to the normal condition. This
is because, for latching relays, the alarm LED reflects the status of the relay, regardless of the alarm
condition.