Scanner instruction manual, Setting up the interlock relay (force on) feature – Precision Digital PD6080 User Manual

Page 65

Advertising
background image

PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

65

Setting Up the Interlock Relay (Force On) Feature

Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature:

1. Access the SetupRelayAction menu and set the action to off.


2. In the Advanced features – User menu, program any of the digital inputs to Force On any of the

internal relays (1-4). The Advanced Features Menu can be found on page 69.

3. Connect a switch or dry contact between the +5V terminal and the corresponding digital input (dI-1 to

dI-4) terminal.

1

2

3

4

5

6

+5

I1

I2

I3

I4

O1

7

8

O2

O3

9

10

O4

G

DI 1-4

DO 1-4

5 VDC

GND

SW2

SW1

Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front panel LEDs are off) when SW1 & SW2 switches
(above) are closed. If the contacts to these digital inputs are opened, the corresponding front panel LEDs
flash, indicating this condition. The processes being controlled by the interlock relay will stop, and will re-
start only after the interlock relay is re-activated by the digital inputs (switches).
Note: If multiple digital inputs are assigned to the same relay, then the corresponding logic is (AND) – i.e.
both switches must be closed to trip the relay.

Advertising
This manual is related to the following products: