PD6080/PD6081 Super Snooper Modbus

Scanner Instruction Manual

29

Display

Parameter

Action/Setting Description

DLY 1*

Delay 1*

*Enter relay 1-8 time delay setup

On 1

On 1

Set relay 1 On time delay

OFF 1

Off 1

Set relay 1 Off time delay

break

Break

Set relay condition if communication break detected

No act

No action

Ignore break condition. No change in relay state when
Communications Break detected.

On

On

Relay goes to alarm condition when break detected. Relay turns on
when Communications Break detected.

Off

Off

Relay goes to non-alarm condition when break detected. Relay turns
off when Communications Break detected.

Aout

Analog output

Enter the Analog Output scaling menu

AOut 1*

Aout channel

Analog Output source channel (*1-3)

Dis 1

Display 1

Program the first Display value for the Analog Output.

Out 1

Output 1

Program the first Output value that corresponds to the Display 1 value
for the Analog Output. (e.g. 4.000 mA).

Dis 2

Display 2

Program the second Display value for the Analog Output.

Out 2

Output 2

Program the second Output value that corresponds to the Display 2
value for the Analog Output. (e.g. 4.000 mA). (e.g. 20.000 mA)

serial

Serial

Enter Serial menu

SCan.ID

Scan ID

Enter Scan ID of the meter being polled (1-247)

baud

Baud Rate

Select Baud Rate (Choices: 300/600/1200/2400/4800/9600/19,200)

(Must match that of other devices)

Tr dly

Transmit Delay

Enter Transmit Delay
(Master’s delay must be greater than Snooper or slave devices)

parity

Parity

Select Parity (Even, Odd, None 1-Stop, or None 2-Stop)

(Must match that of other devices)

t-byt

Byte-to-byte Timeout

Enter the timeout value allowed between received bytes.

(This is used to fix communication problems with slow devices).

pass

Password

Enter the Password menu

Pass 1

Password 1

Set or enter Password 1

Pass 2

Password 2

Set or enter Password 2

Pass 3

Password 3

Set or enter Password 3

unloc

Unlocked

Program password to lock scanner

locd

Locked

Enter password to unlock scanner

999999
-99999

Flashing

Over/under range condition