Reference 4205/5205-TS-104S-PDPS

♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 101 of 128

July 12, 2007

4.3.2

Client 1 Status

Status
Register

Name Description

10250

Socket State Value
(socket 1)

This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for connection
1 = Transmit message if ready
2 = Receive packet and process message
3 = Process multiple messages in packet
50 = Send TestFr Act
51 = Wait for TestFr Con
60 = Send sequence (S-Format) message
1000 = Close Socket
1001 = Wait for socket to close

10251

Socket Open Count
(socket 1)

This word contains the number of times the socket
listen function executed.

10252

Socket Close Count
(socket 1)

This word contains the number of times an active
close function executed.

10253

Socket Connect Count
(socket 1)

This word contains the number of times a
connection was established with the remote host
unit.

10254

10263

Host IP Address
(socket 1)

IP address of the client connected to the server.

10264

StartDT active (socket 1)

This word contains the current StartDT state as
follows:
0 = The module has not received the most recent
STARTDT request through this socket or there
has been no communication with the remote host
unit.
1 = The module has received the most recent
STARTDT request through this socket (therefore
will be reporting data to the remote client
connected through this socket).


4.4 LED

Indicators

Troubleshooting the operation of the IEC Slave port can be performed using
several methods.

The first and quickest is to scan the LEDs on the module to determine the
existence and possibly the cause of a problem. This section provides insight into
the operation of the Serial Port status LEDs. Information on the module's other
LEDs can be found in the ProLinx Reference Guide.