Protocol Implementation

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 39 of 128

July 12, 2007

Deadband –

Sets the deadband for each Measured point. If the value changes

from more than the configured deadband , the module will generate an event for
this point.

IV DB Bit –

This feature allows the application to set the invalid (IV) quality bit of

the protocol for all the monitored ASDU types supported. If you enable this
feature, the processor can determine the individual IV quality bit status of each
point you configured.

The following parameters must be configured in order to use this feature:

Cyclic Set IV Time : 10 #Number of sec intervals

IV Check Delay Time : 2 #Number of sec intervals between

#investigation

IV Fail Count : 2 #Number of IV failures recognized

#before reporting

To disable this feature, set the IV Fail Count parameter to 0. If used, the Cyclic
Set IV Time parameter must be at least 3 times larger than the IV Check Delay
Time.

The Cyclic Set IV Time parameter must be set to determine how frequently the IV
Checks will be performed. If the IV bit is ON for a number of times given by the IV
Fail Count parameter the module will consider the point as invalid. The following
illustration shows how these parameters are implemented: