File transfer

(Station-specific parameter, mark 'X' if function is used)

File transfer in monitor direction

Transparent

file

Transmission of disturbance data of protection equipment

Transmission of sequence of events

Transmission of sequence of recorded analogue values

File transfer in control direction

Transparent

file

Background scan

(Station-specific parameter, mark 'X' if function is only used in the standard
direction, 'R' if only used in the reverse direction, and 'B' if used in both
directions)

Background

scan

Definition of time outs

Paramete
r

Default
Value

Remarks

Selected
Value

t

0

60 seconds

Time-out of connection establishment

60 seconds

t

1

15 seconds

Time-out of send or test APDUs

t

2

10

seconds

Time-out for acknowledges in case of no data messages
(t

2

< t

1

)

t

3

20

seconds

Time-out for sending test frames in case of a long idle
time

Maximum range of values for all time-outs: 1 to 255 seconds, accuracy 1 second.

Maximum number of outstanding I format APDUs k and latest acknowledge
APDUs (w)

Paramete
r

Default
Value

Remarks

Selected
Value

k

12 APDUs

Maximum difference receive sequence number to send
state variable (Maximum value is 19)

w

8 APDUs

Latest acknowledge after receiving w I format APDUs

Maximum range of values k: 1 to 32767 (2

15

–1) APDUs, accuracy 1 APDU

Maximum range of values w: 1 to 32767 (2

15

–1) APDUs, accuracy 1 APDU

(Recommendation: w should not exceed two-thirds of k).

Port number

Parameter Value

Remarks

Port number

2404

In all cases