ProSoft Technology 5205-104S-PDPS User Manual

Page 11

Advertising
background image

Customizing the Sample Configuration File

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 11 of 128

July 12, 2007

Parameter Data Structure

SPC3 evaluates the first seven data bytes (without user prm data), or the first
eight data bytes (with user prm data). The first seven bytes are specified
according to the standard. The eighth byte is used for SPC3-specific
communications. The additional bytes are available to the application.

Byte Bit

Position

Designation

7 6 5 4 3 2 1 0

0 Lock

Reg

Unio
Req

Sync
Req

Free
Req

WD
on

Res Res Res Station

status

1

WD_Fact_1

2

WD_Fact_2

3

MinTSDR

4

Ident_Number_High

5

Ident_Number_Low

6

Group_Ident

7

Spec_User_Prm_Byte

8 to 243

User_Prm_Data

Byte 7

Spec_User_Prm_Byte

Bit Name

Significance

Default

State

0

Dis_Startbit

The start bit monitoring in the receiver
is switched off with this bit

Dis_Startbit = 1,
That is, start bit monitoring is switched off.

1

Dis_Stopbit

Stop bit monitoring in the receiver is
switched off with this bit

Dis_Stopbit = 0
That is, stop bit monitoring is not switched
off.

2

WD_Base

This bit specifies the time base used
to clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms

WD_Base = 0
That is, the time base is 10 ms.

3 to 4

Res

To be parameterized with 0

0

5

Publisher_Enable

DXB-publisher-functionality of the
SPC3 is activated with this bit

Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegramme are processed

6 to 7

Res

To be parameterized with 0

0

Advertising