M_st_na time type, M_me_na scan events, M_me_na time type – ProSoft Technology 5205-104S-PDPS User Manual

Page 21: M_me_nb scan events, M_me_nb time type, M_me_nc scan events, M_me_nc time type, M_it_na time type

Advertising
background image

Customizing the Sample Configuration File

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 21 of 128

July 12, 2007

M_ST_NA Time Type

M_ST_NA Time Type : 2 #0=None, 2=CP56 time

This parameters defines the time format used with data events. 0=None and
2=CP56 time formats.

M_ME_NA Scan Events

M_ME_NA Scan Events : 1 #0=No scanning, 1=scan for events

Determines if events of this point type will be generated by the module. If 0, then
events will not be generated. If 1, events will be scanned and generated on
change.

M_ME_NA Time Type

M_ME_NA Time Type : 2 #0=None, 2=CP56 time

This parameter defines the time format used with data events. 0=None and
2=CP56 time formats.

M_ME_NB Scan Events

M_ME_NB Scan Events : 1 #0=No scanning, 1=scan for events

Determines if events of this point type will be generated by the module. If 0, then
events will not be generated. If 1, events will be scanned and generated on
change.

M_ME_NB Time Type

M_ME_NB Time Type : 2 #0=None, 2=CP56 time

This parameters defines the time format used with data events. 0=None and
2=CP56 time formats.

M_ME_NC Scan Events

M_ME_NC Scan Events : 1 #0=No scanning, 1=scan for events

Determines if events of this point type will be generated by the module. If 0, then
events will not be generated. If 1, events will be scanned and generated on
change.

M_ME_NC Time Type

M_ME_NC Time Type : 2 #0=None, 1=CP24, 2=CP56 time

This parameters defines the time format used with data events. 0=None and
2=CP56 time formats.

M_IT_NA Time Type

M_IT_NA Time Type : 2 #0=None, 2=CP56 time

This parameters defines the time format used with data events. 0=None and
2=CP56 time formats.

Advertising