4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

Protocol Implementation

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

Page 52 of 128

ProSoft Technology, Inc.

July 12, 2007

In the example above, the module would send a TESTFR.ACT message 30
seconds after receiving the last message:

If the module does not receive the TESTFR.con message within a certain
amount of time, it will timeout and close the connection. You can configure the
timeout period using the following parameter:

t1 timeout set value : 15 #timeout of send or test ASDU

When closing the connection, the module can be configured to clear all the
messages in its queue. The following parameter is used to implement this task:

Clear queue on close: 1 #Clear the queue when connection closed

#(0=No, 1=Yes)

The configuration above would cause to module to delete all pending
messages/events while closing the connection to the client.