Baud rate monitoring, Response time monitoring – ProSoft Technology 5205-104S-PDPS User Manual

Page 88

Advertising
background image

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

Diagnostics and Troubleshooting

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

Page 88 of 128

ProSoft Technology, Inc.

July 12, 2007

Bit 4, 5

10 = Data Exchange State is Normal. The SPC3 has a correct configuration.

Bits 6, 7

Watchdog

Timer

Automatic Baud Rate Identification

The SPC3 is able to identify the baud rate automatically. The "baud search" state
is located after each RESET and also after the watchdog (WD) timer has run out
in the "Baud_Control_state." As a rule, SPC3 begins the search for the set rate
with the highest baud rate. If no SD1 telegram, SD2 telegram, or SD3 telegram
was received completely and without errors during the monitoring time, the
search continues with the next lowest baud rate.

After identifying the correct baud rate, SPC3 switches to the "Baud_Control"
state and monitors the baud rate. The monitoring time can be parameterized
(WD_Baud_Control_Val). The watchdog works with a clock of 100 Hz (10
milliseconds). The watchdog resets each telegram received with no errors to its
own station address. If the timer runs out, SPC3 again switches to the baud
search state.

Baud Rate Monitoring

The located baud rate is constantly monitored in 'Baud_Control.' The watchdog is
reset for each error-free telegram to its own station address. The monitoring time
results from multiplying both 'WD_Baud_Control_Val' (user sets the parameters)
by the time base (10 ms). If the monitoring time runs out, WD_SM again goes to
'Baud_Search'. If the user carries out the DP protocol (DP_Mode = 1, see Mode
register 0) with SPC3, the watchdog is used for the "DP_Control' state, after a
'Set_Param telegram' was received with an enabled response time monitoring
'WD_On = 1.' The watchdog timer remains in the baud rate monitoring state
when there is a switched off 'WD_On = 0' master monitoring. The PROFIBUS DP
state machine is also not reset when the timer runs out. That is, the slave
remains in the DATA_Exchange state, for example.

Response Time Monitoring

The 'DP_Control' state serves response time monitoring of the DP master
(Master_Add). The set monitoring times results from multiplying both watchdog
factors and multiplying the result with the momentarily valid time base (1 ms or
10 ms):

TWD = (1 ms or 10 ms) * WD_Fact_1 * WD_Fact_2 (See byte 7 of the

parameter setting telegram.)

The user can load the two watchdog factors (WD_Fact_1, and WD_Fact_2) and
the time base that represents a measurement for the monitoring time via the
'Set_Param telegram' with any value between 1 and 255.

EXCEPTION: The WD_Fact_1=WD_Fact_2=1 setting is not permissible. The
circuit does not check this setting.

Monitoring times between 2 ms and 650 s - independent of the baud rate - can
be implemented with the permissible watchdog factors. If the monitoring time
runs out, the SPC3 goes again to 'Baud_Control,' and the SPC3 generates the

Advertising