Diagnostics and Troubleshooting

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 89 of 128

July 12, 2007

'WD_DP_Control_Timeout-Interrupt'. In addition, the DP_State machine is reset,
that is, generates the reset states of the buffer management.

If another master accepts SPC3, then there is either a switch to 'Baud_Control"
(WD_On = 0), or there is a delay in 'DP_Control' (WD_On = 1), depending on the
enabled response time monitoring (WD_On = 0).

Status Register [1]

SPC3 ASIC slave status information provided to the master.

Baud rate:
The baud rates SPC3 found

Bits
0 - 3

0000 = 12 MBaud
0001 = 6 MBaud
0010 = 3 MBaud
0011 = 1.5 MBaud
0100 = 500 kBaud
0101 = 187.5 kBaud
0110 = 93.75 kBaud
0111 = 45.45 kBaud
1000 = 19.2 kBaud
1001 = 9.6 kBaud
Rest = Not possible

SPC3-Release:
Release no. for SPC3

Bits
4 - 7

0000 = Release 0
Rest = Not possible


Diagnostic State

0 = Normal Operation or not in data exchange with Status Register [0] Bit

0x20 set.

1 = Not in data exchange state with the Status Register [0] bit 0x20 not set or

normal operation with the Status Register [0] bit 0x20 not set.

3 = Not in a defined state or in module state 1, 2 or 3.
4 = Normal operation with Status Register [0] bit 0x20 set

PROFIBUS Input Counter

Input counter is incremented each time the input data is updated.

PROFIBUS Output Counter

Output counter is incremented each time the output data is updated.