C_rc_na, C_se_na and c_se_nb – ProSoft Technology 5205-104S-PDPS User Manual
Page 48

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone
Protocol Implementation
IEC-60870-5-104 to PDPS Communication Module with Time Stamp
Page 48 of 128
ProSoft Technology, Inc.
July 12, 2007
Configure the parameters below to set the duration of the short and long pulses:
Short Pulse Time : 2000 #MSec for short pulse command
Long Pulse Time : 10000 #MSec for long pulse command
C_RC_NA
The step-point command uses one byte with byte-addressing.
For example, if you configured the following points:
# Monitor Monitor
# Point # DB Address Point # DB Addr
# ------- ---------- ------- -------
START
300 40 0 0
301 60 0 0
302 81 0 0
END
These points would be used as follows:
Inf. Object Address
Module Database Address
300
Low Byte of word 20
301
Low Byte of word 30
302
High Byte of word 40
C_SE_NA and C_SE_NB
The measured normalized point command uses one word with word-addressing.
For example, if you configured the following points:
# Monitor Monitor Require
# Point # DB Address Point # DB Addr Select
# ------- ---------- ------- ------- -------
START
400 10 0 0 0
401 12 0 0 0
402 18 0 0 0
END
These points would be used as follows:
Inf. Object Address
4205/5205-TS-104S-PDPS Module Database Address
400 Word
10
401 Word
12
402 Word
18
The measured normalized points use a data representation defined by the
protocol specification, where each bit represents a value as follows:
Bit 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Value S 2
–1
2
-2
2
-3
2
-4
2
-5
2
-6
2
-7
2
-8
2
-9
2
–10
2
–11
2
–12
2
–13
2
–14
2
–15
Ex: a value of 4000hex is interpreted as 0.5