Mailbox commands, Mailbox structure, Mailbox from plc to gw – ProSoft Technology 5205-104S-PDPS User Manual

Page 63: Mailbox from gw to plc, Example raw database exchange

Advertising
background image

Protocol Implementation

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 63 of 128

July 12, 2007

Mailbox Commands

Start Stop

Direction

Description

100

101

PLC to GW

Event Data

150

151

PLC to GW

Database write transfer

160

161

GW to PLC

Database read transfer

200 200

Both

Set

Time

201 201

Both

Get

Time

202

202

Both

Get Event Buffer Counts

PLC = PROFIBUS master interface in PLC

GW = ProLinx Gateway

NOTES:

The block number for each device must be changed to trigger an operation.

The I/O data area is owned exclusively by only the PLC or GW.

A timeout must be implemented in the PLC in case the GW is not present.

Mailbox Structure

Mailbox From PLC to GW

Start Byte

End Byte

Description

0

0

Block number of data in block

1

1

Block number of data requested

2

198

Data for block

199

199

Block number of data in block


Mailbox From GW to PLC

Start Byte

End Byte

Description

0

0

Block number of data in block

1

1

Block number last requested by PLC

2

198

Data for block

199

199

Block number of data in block


Example Raw Database Exchange

Start Byte

End Byte

Description

0

0

150 (Raw data write)

1

1

160 (Raw data read)

2

3

Start register in database for write

4

5

Number of registers to write (1 to 94)

6

7

Start register in database for read

8

9

Number of registers to read (1 to 96)

10

197

Words to write to the database

198 198

Reserved

199

199

150 (Raw data write)