4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

Protocol Implementation

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

Page 50 of 128

ProSoft Technology, Inc.

July 12, 2007

Example:

In the following example, with the following data points for data type M_SP_NA
configured:

[M_SP_NA_1 104]

# Point # DB Address Group(s)

# ------- ---------- --------

START

100 1600 80000000 # Periodic Poll

101 1601 00000002 # Group 1 Interrogation

102 1602 00000002 # Group 1 Interrogation

103 1603 00000004 # Group 2 Interrogation

END

And the Cyclic data transmission parameter configured as follows:

Cyclic data transmission : 20000 #Numb of milliseconds between cyclic updates

The client unit sends the following requests:

General Interrogation for Group 1 every 12 seconds
General Interrogation for Group 2 every 15 seconds

The following illustration shows how the communication would be performed
between the client and the 104S module.