4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

Customizing the Sample Configuration File

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

Page 28 of 128

ProSoft Technology, Inc.

July 12, 2007

This section takes the following parameters:

Point

#:

DB

Address:

Monitor Point #:
Monitor

DB

Addr:

Require

Select:

Each point is one bit and the DB Address value corresponds to the bit offset in
the database.

1.1.17

[C_DC_NA_1 104] Section

This section defines the double point command database for the server
emulated. This information is sourced from the remote client and is transferred to
the database. Each point occupies two bits in the database. You can associate a
command with a monitored double point database value to coordinate the
command/monitor operation. You must enter the correct Monitor Point # and
Monitor DB Addr values in the table. If the Require Select parameter is not set to
zero, a select command must be received before an execute command will be
processed.

This section takes the following parameters:

Point

#:

DB

Address:

Monitor Point #:
Monitor

DB

Addr:

Require

Select:

Each point is two bits and the DB Address value corresponds to the bit offset in
the database.

1.1.18

[C_RC_NA_1 104] Section

This section defines the step command database for the server emulated. This
information is sourced from the remote client and is transferred to the database.
Each point occupies a byte in the database. The control value can be associated
with a monitored point as described in the previous example.

This section takes the following parameters:

Point

#:

DB

Address:

Monitor Point #:
Monitor

DB

Addr:

Each point is one byte and the DB Address value corresponds to the byte offset
in the database.