Example – periodic monitor polling – ProSoft Technology 5205-104S-PDPS User Manual

Page 41

Advertising
background image

Protocol Implementation

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 41 of 128

July 12, 2007

The module will periodically send all points configured for periodic/cyclic poll
(0x80000000) at every x milliseconds, where x is configured with the following
parameter:

Cyclic data transmission: 20000 #Numb of milliseconds between cyclic

#updates

Example – Periodic Monitor Polling:

If the following point is configured for monitor polling:

[M_ME_NB_1]

#

# Each point is one word and the DB Address value corresponds to the

# word offset into the database.

#

# Default

# Point # DB Address Group(s) Deadband IV DB Bit

# ------- ---------- -------- -------- ---------

START

100 0 80000000 0 0

END

If you configure the periodic polling for 10 seconds (10000 milliseconds) as
follows:

Cyclic data transmission : 10000 #Numb of milliseconds between

#cyclic updates

The following illustration shows the communication procedure:

Therefore, the point configured for a cyclic poll is periodically reported to the
master.

You may also create groups of points allowing the master to poll certain points
more frequently than other points. The master may send requests for different
groups as follows:

General Interrogation (station)
General Interrogation for Group 1