Use ip list, Override startdt – ProSoft Technology 5205-104S-PDPS User Manual

Page 15

Advertising
background image

Customizing the Sample Configuration File

4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 15 of 128

July 12, 2007

M_ME_NC Priority : 2 #Unique index for this data type in queue

#(0-5)

M_IT_NA Priority : 6 #Unique index for this data type in queue

#(0-5)

# This section is used to define the parameters utilized for the Invalid Bit

# Monitoring. If this feature is not used, set the parameters to zero. If used,

# the Cyclic Set IV Time must be at least 3 times larger than the IV Check Delay

# Time. If the IV Fail Count parameter is zero, the feature will be disabled.

Cyclic Set IV Time : 60 #Number of sec intervals between IV sets

IV Check Delay Time : 15 #Number of sec intervals between investigation

IV Fail Count : 3 #Number of IV failures recognized before

#reporting

# Event configuration

Event Scan delay : 1 #MSec between event scanning (0-65535) 0=Disable

M_SP_NA Scan Events : 1 #0=No scanning, 1=scan for events

M_SP_NA Time Type : 2 #0=None, 2=CP56 time

M_DP_NA Scan Events : 1 #0=No scanning, 1=scan for events

M_DP_NA Time Type : 2 #0=None, 2=CP56 time

M_ST_NA Scan Events : 1 #0=No scanning, 1=scan for events

M_ST_NA Time Type : 2 #0=None, 2=CP56 time

M_ME_NA Scan Events : 1 #0=No scanning, 1=scan for events

M_ME_NA Time Type : 2 #0=None, 2=CP56 time

M_ME_NB Scan Events : 1 #0=No scanning, 1=scan for events

M_ME_NB Time Type : 2 #0=None, 2=CP56 time

M_ME_NC Scan Events : 0 #0=No scanning, 1=scan for events

M_ME_NC Time Type : 2 #0=None, 2=CP56 time

M_IT_NA Time Type : 2 #0=None, 2=CP56 time

Modify each parameter based on the needs of your application.

Use IP List

Use IP List : 0 #Use IP list to validate connection

#(0=No, 1=Yes)

This parameter specifies if the IP address of the host connected to the system
will be validated. If the parameter is set to 0, any host may connect to the unit. If
the parameter is set to 1, only hosts in the IP list will be permitted to connect to
the unit.

Override StartDT

Override StartDT : 1 #Used to ignore STARTDT/STOPDT state

#(0=No, 1=Yes)

This parameter is used when testing the unit with a simulator or with a client unit
that does not meet the IEC 60870-5-104 specification. After the host connects to
the system, it will send a STARTDT.ACT U-format message to the unit to permit
the unit to start sending data. If the client does not support this requirement, set
the parameter to a value of 1. Set the parameter to 0 if the unit sends the
STARTDT.ACT message.