Specification Description
Dimensions

Standard: 5.20H x 2.07W x 4.52D in. (13.2cmH x 5.25cmW x 11.48cmD)
Extended: 5.20H x 2.73W x 4.52D in. (13.2cmH x 6.934cmW x 11.48cmD)

LED Indicators

Power and Module Status
Application Status
Serial Port Activity LED
Serial Activity and Error LED Status

Configuration Serial Port

DB-9M RS-232 only
No hardware handshaking

Ethernet Port (Ethernet modules
only)

RJ45 Connector
Link and Activity LED indicators

Application Serial Ports

RS-232/422/485
RS-232 handshaking configurable
RS-422/485 screw termination included

Serial Port Isolation

2500V RMS port signal isolation per UL 1577
3000V DC min. port to ground and port to logic power isolation

Shipped with Each Unit

Mini-DIN to DB-9M serial cables
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)


4.1.4

Port Physical and Protocol Specifications

104 Slave Port Specifications

The 104S module acts as a gateway between the IEC-870-5-104, other protocols
and networks, as well as several proprietary interfaces. A 4000-word register
space in the module exchanges data between the two protocols.

General specifications include:

Support for the storage and transfer of up to 4000 registers between

protocols

User-definable module memory usage
Storage of IEC time used in module is available in the database
Configuration via a user-generated text file (downloadable to the module)
Protocol implementation conforms to the IEC-870-5-104 specification with

fully configurable parameters

Priority

Queues

Invalid Bit Monitoring
Supports Redundant Connection

Driver Protocol Specifications

General Parameters

Internal Database

4000 registers (words) available

Communication parameters

Port 0: Baud Rate = 110 to 38.4K baud
Port 1,2,3: Baud Rate = 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 5 or 8 bits
Parity: None, Even, Odd
RTS Timing Delays: 0 to 65535 milliseconds