Reference

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

Page 102 of 128

ProSoft Technology, Inc.

July 12, 2007

LEDs for Port 0 Serial Port

Some ProLinx modules will include an extra three serial ports. Each of these
serial ports has two LEDs indicating status.

LED Color

Description

Off

No activity on the port.

Port 0 – ACT

Green Flash

The port is either actively transmitting or receiving data

Off

Normal state. When off and Port Active led is indicating
activity, there are no communication errors

Port 0 – ERR

Red On or
Flashing

Activity on this led indicates some communication error was
detected, either during transmit or receive


4.5 Command

Qualifiers

Qualifier Code

Description

0

No additional definitions (Module will use Long duration pulse for this qualifier
selection).

1

Short pulse duration (circuit breaker), determined by user-set parameter in
module. This is supported in the module for single and dual point commands.

2

Long duration pulse (control relay), duration determined by user-set parameter
in module. This is supported in the module for single and dual point commands.

3

Persistent output of control. This is supported in the module for all output data
types.

4 to 8

Reserved for standard definitions of standard – NOT SUPPORTED

9 to 15

Reserved for the selection of other predefined functions – NOT SUPPORTED

16 to 31

Reserved for special use (private range) – NOT SUPPORTED


4.6 Parameter

Qualifiers

Type of Parameter

Description

0 Not

used.

1

Threshold value (deadband). This parameter is used as the value of
variation from the last reported event value to generate events. Each
measured value has a user-assigned deadband value. The low and high
limit parameter values are computed using the value entered for each
measure data point. This parameter can be set and read by the controlling
device (client).

2

Smoothing factor (filtered time constant) – NOT SUPPORTED

3

Low limit for transmission of metered values. This value is used as the lower
limit for event generation. The value of this parameter is determined based
on the value of the last reported event and the deadband set for the specific
point. This parameter can be read by the controlling device (client).

4

High limit for transmission of measured values. This value is used as the
upper limit for event generation. The value of this parameter is set based on
the value of the last reported event and the deadband for the specific point.
This parameter can be read by the controlling device (client).

5 to 31

Reserved for standard definitions of standard – NOT SUPPORTED

32 to 63

Reserved for special use – NOT SUPPORTED.