1.1.21

[C_SE_NC_1 104] Section

This section defines the short-float setpoint database for the server emulated.
This information is sourced from the remote client and is transferred to the
database. Each point occupies a double-word position in the database. If the
Require Select parameter is not set to zero, a select command must be received
before an execute command will be processed.

This section takes the following parameters:

Point

#:

DB

Address:

Monitor Point #:
Monitor

DB

Addr:

Require

Select:

Each point is two words and the DB Address value corresponds to the double-
word offset in the database.

The database address should be located in a database area that is being
constantly moved from the module to the processor. You should configure the
DB Address parameter in an area that is on a Backplane Command Function 2.

1.1.22 Group

Definition

One aspect of the point configuration database that leads to confusion is the
group definition field. This assignment for each point assigns a point to one or
more interrogation groups. Use of interrogation groups permits the controlling
unit to interface with a specific set of data. Refer to the IEC 60870-5-104
standard for a full discussion of interrogation groups. A specific group, Periodic
data group, reports data points on a set frequency. The frequency is set in the
Cyclic Data Transmission

parameter in the configuration file. Remember that a

point can be assigned to more than one group:

Group Code

Description

0x00000001

Interrogated by general interrogation (station or global)

0x00000002

Interrogated by group 1 interrogation

0x00000004

Interrogated by group 2 interrogation

0x00000008

Interrogated by group 3 interrogation

0x00000010

Interrogated by group 4 interrogation

0x00000020

Interrogated by group 5 interrogation

0x00000040

Interrogated by group 6 interrogation

0x00000080

Interrogated by group 7 interrogation

0x00000100

Interrogated by group 8 interrogation

0x00000200

Interrogated by group 9 interrogation

0x00000400

Interrogated by group 10 interrogation

0x00000800

Interrogated by group 11 interrogation

0x00001000

Interrogated by group 12 interrogation

0x00002000

Interrogated by group 13 interrogation

Advertising