Iec 60870-5-104 server interoperability document, System or device, Application layer – ProSoft Technology 5205-104S-PDPS User Manual

Page 107: Transmission mode for application data, Common address of asdu

Advertising
background image

Reference 4205/5205-TS-104S-PDPS

♦ ProLinx Standalone

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

ProSoft Technology, Inc.

Page 107 of 128

July 12, 2007

4.8

IEC 60870-5-104 Server Interoperability Document

This companion standard presents sets of parameters and alternatives from
which subsets have to be selected to implement particular telecontrol systems.
Certain parameter values, such as the number of octets in the COMMON
ADDRESS of ASDUs represent mutually exclusive alternatives. This means that
only one value of the defined parameters is admitted per system. Other
parameters, such as the listed set of different process information in command
and in monitor direction allow the specification of the complete set or subsets, as
appropriate for given applications. This clause summarizes the parameters of the
previous clauses to facilitate a suitable selection for a specific application. If a
system is composed of equipment stemming from different manufacturers it is
necessary that all partners agree on the selected parameters.

NOTE:

In addition, the full specification of a system may require individual

selection of certain parameters for certain parts of the system, such as the
individual selection of scaling factors for individually addressable measured
values.

The selected parameters should be marked in the white boxes as follows:

Function or ASDU is not used

Function or ASDU is used as standardized (default)

R

Function or ASDU is used in reverse mode

B

Function or ASDU is used in standard and reverse mode

The possible selection (blank, X, R, B) is specified for each specific clause or
parameter.

A black check box indicates that the option cannot be selected in this companion
standard.

4.8.1

System or device

System definition

Controlling station definition (Master)

Controlled station definition (Slave)

4.8.2 Application

Layer

Transmission mode for application data

Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4,
is used exclusively in this companion standard.

Common address of ASDU

(System-specific parameter)

One octet ⌧ Two octets