4205/5205-TS-104S-PDPS ♦ ProLinx Standalone

Protocol Implementation

IEC-60870-5-104 to PDPS Communication Module with Time Stamp

Page 54 of 128

ProSoft Technology, Inc.

July 12, 2007

The protocol specification explains that the qualifier value for these commands
should be configured as:

Bits Value

Description

0 Not

Used

1

Threshold Value (Deadband)

2

Smoothing Factor (filter time constant) – Not Supported

3

Low Limit Transmission of Measured Value

4

High Limit Transmission of Measured Value


1 to 6

5..31 Reserved
0 No

Change

7

1 Change
0 Operation

8

1

Not in Operation

For the 4205/5205-TS-104S-PDPS module, the Low Limit and High Limit
parameters cannot be changed by command, because these values are
calculated as follows:

Low Limit = (LAST REPORTED VALUE) – Deadband

High Limit = (LAST REPORTED VALUE) + Deadband

These commands must be sent to a specific Information Object Address. The
4205/5205-TS-104S-PDPS module associates each monitor measured point with
a parameter point through the following configuration parameters:

M_ME_NA Parameter Offset : 2000 #M_ME_NA IOA offset for parameter data

M_ME_NB Parameter Offset : 2000 #M_ME_NB IOA offset for parameter data

M_ME_NC Parameter Offset : 2000 #M_ME_NC IOA offset for parameter data

Example:

If the following monitored measured points are configured:

[M_ME_NA_1 104]

#

# Default

# Point # DB Address Group(s) Deadband IV DB Bit

# ------- ---------- -------- -------- ---------

START

400 10 00000002 100 # P1 suction pressure

401 11 00000002 100 # P1 discharge pressure

402 12 00000002 100 # P2 suction pressure

403 13 00000002 100 # P2 discharge pressure

404 14 00000002 100 # Station discharge pressure

405 15 00000002 100 # VSD speed

406 16 00000002 100 #

407 17 00000002 100 #

408 18 00000002 100 #

409 19 00000002 100 #

END