Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 100

Advertising
background image

Cycle and reaction times

5.3 Response time

CPU 31xC and CPU 31x, Technical data

5-18

Manual, Edition 08/2004, A5E00105475-05

Calculation

The (longest) response time is the sum of:

Table 5-11 Formula: Longest response time

2 x process image transfer time for the inputs

+

2 x process image transfer time for the outputs

+

2 x program processing time

+

2 × operating system processing time

+

2 x program processing time

+

4 x PROFINET IO update time (only if PROFINET IO is used.)

+

4 x DP cycle time on PROFIBUS DP (only if PROFIBUS DP is used.)

+

I/O delay

=

Longest response time

Equivalent to the sum of 2 x the cycle time + I/O delay time + 4 x times the PROFINET IO

update time or 4 x times the DP cycle time on PROFIBUS DP.

See also

Overview (Page 5-14)

5.3.4

Reducing the response time with direct I/O access

Reducing the response time

You can reach faster response times with direct access to the I/O in your user program, e.g.

with

L PIB or

T PQW

you can partially avoid the response times described above.

Note
You can also achieve fast response times by using process interrupts.

See also

Shortest response time (Page 5-16)
Longest response time (Page 5-17)

Advertising