Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 182

Advertising
background image

Technical data of CPU 31x

7.4 CPU 315-2 DP

CPU 31xC and CPU 31x, Technical data

7-16

Manual, Edition 08/2004, A5E00105475-05

Technical data
Diagnostic buffer

Yes

Number of entries (not configurable)

Max. 100

Communication functions
PG/OP communication

Yes

Global data communication

Yes

Number of GD circuits

8

Number of GD packets

Sending stations

Receiving stations

Max. 8
Max. 8
Max. 8

Length of GD packets

Consistent data

max. 22 bytes
22 bytes

S7 basic communication

Yes

User data per request

Consistent data

max. 76 bytes
76 bytes (for X_SEND or X_RCV)
64 bytes (for X_PUT or X_GET as the server)

S7 communication

Yes

As server

Yes

as client

Yes (via CP and loadable FBs)

User data per request

Consistent data

Max. 180 bytes (with PUT/GET)
64 byte (as the server)

S5-compatible communication

Yes (via CP and loadable FCs)

Number of connections

16

can be used for

PG communication

Reserved (default)

Configurable

Max. 15
1
1 to 15

OP communication

Reserved (default)

Configurable

Max. 15
1
1 to 15

S7-based communication

Reserved (default)

Configurable

Max. 12
12
0 to 12

Routing

Yes (max. 4)

Interfaces
1st interface
Type of interface

Integrated RS485 interface

Physics

RS 485

electrically isolated

No

Interface power supply

(15 to 30 VDC)

max. 200 mA

Advertising