Communication

3.4 DPV1

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

3-33

Interrupt blocks with DPV1 functionality

Table 3-13 Interrupt blocks with DPV1 functionality

OB

Functionality

OB 40

Process interrupt

OB 55

Status interrupt

OB 56

Update interrupt

OB 57

Vendor-specific interrupt

OB 82

Diagnostic interrupt

Note
You can now also use organizational blocks OB40 and OB82 for DPV1 interrupts.

System blocks with DPV1 functionality

Table 3-14 System function blocks with DPV1 functionality

SFB

Functionality

SFB 52

Read data record from DP slave or centralized module

SFB 53

Write data record to DP slave or centralized module

SFB 54

Read additional alarm information from a DP slave or a centralized module in the

relevant OB.

SFB 75

Set any interrupts for intelligent slaves

Note
You can also use SFB 52 to SFB 54 for centralized I/O modules. SFBs 52 to 54 can also be

used for PN IO.

Reference

For further information on the blocks mentioned earlier, refer to the reference manual

System Software for S7-300/400: System and Standard Software, or directly to the

STEP 7 Online Help.

See also

PROFIBUS DP (Page 3-2)