Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 195

Advertising
background image

Technical data of CPU 31x

7.6 CPU 317-2 DP

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

7-29

Technical data
S7 signaling functions
Number of stations that can be logged on for

signaling functions

32
(depends on the number of connections

configured for PG / OP and S7 basic

communication)

Process diagnostics messages

Yes

Simultaneously enabled interrupt S blocks

60

Testing and commissioning functions
Status/control variables

Yes

Variables

Inputs, outputs, memory bits, DBs, timers,

counters

Number of variables

Of those as status variable

Of those as control variable

30
Max. 30
Max. 14

Forcing

Variables

Inputs/Outputs

Number of variables

Max. 10

Block status

Yes

Single step

Yes

Breakpoints

2

Diagnostic buffer

Yes

Number of entries (not configurable)

Max. 100

Communication functions
PG/OP communication

Yes

Global data communication

Yes

Number of GD circuits

8

Number of GD packets

Sending stations

Receiving stations

Max. 8
Max. 8
Max. 8

Length of GD packets

Consistent data

max. 22 bytes
22 bytes

S7 basic communication

Yes

User data per request

Consistent data

max. 76 bytes
76 bytes (for X_SEND or X_RCV)
76 bytes (for X_PUT or X_GET as the server)

S7 communication

Yes

As server

Yes

as client

Yes (via CP and loadable FBs)

User data per request

Consistent data

Max. 180 bytes (with PUT/GET)
160 byte (as the server)

S5-compatible communication

Yes (via CP and loadable FCs)

Advertising