Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 97

Advertising
background image

Cycle and reaction times

5.3 Response time

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

5-15

DP cycle times in the PROFIBUS DP network

If you have configured your PROFIBUS DP master system in STEP 7, STEP 7 calculates the

typical DP cycle time to be expected. You can then view the DP cycle time of your

configuration on the PG.
The figure below gives you an overview of the DP cycle time. In this example, let us assume

that the data of each DP slave has an average length of 4 bytes.

6 ms

4 ms

2 ms

2

4

8

16

32

1 ms

3 ms

5 ms

7 ms

64

17 ms

1

Bus runtime

Number of DP slaves;
maximum number is
dependent on CPU

Minimum

slave interval

Transmission rate 1.5 Mbit/s

Transmission rate 12 MBit/s

With multi-master operation on a PROFIBUS-DP network, you must make allowances for the

DP cycle time at each master. That is, you will have to calculate the times for each master

separately and then add up the results.

Advertising