Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

6-47

Technical data

Table 6-12 Technical data of digital inputs

Technical data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Module-specific data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Number of inputs

10

24

16

24

Number of these inputs which can be used

for technological functions

8

12

12

16

Cable length

Unshielded

For standard DI: Max. 600 m
For technological functions: No
For standard DI: Max. 1000 m
For technological function at max. counting frequency

Shielded

100 m

100 m

100 m

50 m

Voltage, currents, potentials

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Rated load voltage L+

24 VDC

Polarity reversal protection

Yes

Number of inputs which can be controlled

simultaneously

Horizontal assembly

up to 104 °F

up to 60 °C


10
5


24
12


16
8


24
12

Vertical assembly

up to 104 °F


5


12


8


12

Electrical isolation

Between channels and the backplane bus Yes

Between the channels

No

Permitted potential difference

Between different circuits

75 VDC / 60 VAC

Insulation test voltage

500 VDC

Current consumption

On load voltage L+ (no-load)

Max. 70 mA

Max. 70 mA

Max. 70 mA

Status, interrupts, diagnostics

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Status display

green LED per channel

Interrupts

Yes, if the corresponding channel is configured as interrupt input

For using technological functions, please refer to the

Technological

Functions

Manual.

Diagnostics functions

no diagnostics when operated as standard I/O

For using technological functions, please refer to the

Technological

Functions

Manual.