Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

6-35

Measurement principle

31xC CPUs use the measurement principle of actual value encoding. Here, they operate

with a sampling rate of 1 kHz. That is, a new value is available at the peripheral input word

register once every millisecond. This value can then be read via user program (e.g. L PEW).

The "previous" value is read again if access times are shorter than 1 ms.

Integrated hardware low-pass filter

An integrated low-pass filter attenuates analog input signals of channel 0 to 3. They are

attenuated according to the trend in the figure below.

Attenuation

< 1 %

Attenuation

< 1 0 %

strong

attenuation

100 %

Input frequency

Internal
signal level

400 Hz

63 %

200 Hz

50 Hz

Inadmissible

input frequency

Figure 6-3

Low-pass characteristics of the integrated filter

Note
The maximum frequency of the input signal is 400 Hz.