Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

6-55

Technical data
Voltage output

Short-circuit protection

Yes

Short-circuit current

Typically 55 mA

Current output

No-load voltage

Typically 17 V

Destruction limit for externally applied voltages/currents

Voltage measured between the outputs and M

ANA

Max. 16 V

Current

Max. 50 mA;

Connection of actuators

For voltage outputs

wire connection

wire connection (test lead)


Possible, without compensation of

cable resistance
Not possible

For current outputs

wire connection


Possible