Technical data of CPU 31xC

6.5 CPU 314C-2 PtP and CPU 314C-2 DP

CPU 31xC and CPU 31x, Technical data

6-26

Manual, Edition 08/2004, A5E00105475-05

Technical data

CPU 314C-2 PtP

CPU 314C-2 DP

DP slave

Number of connections

12

Services

PG/OP communication

Yes

Routing

Yes (only if interface is active)

Global data communication

No

S7 basic communication

No

S7 communication

No

Direct data exchange

Yes

Transmission rates

Up to 12 Mbps

Intermediate memory

244 bytes I / 244 bytes O

Automatic baud rate search

Yes (only if interface is passive)

Address areas

Max. 32, with max. 32 bytes each

DPV1

No

GSD file

The latest GSD file is available at:
http://www.ad.siemens.de/support
in the Product Support area

Point-to-point communication

Transmission rates

38.4 kbps half duplex

19.2 kbps full duplex

Cable length

Max. 1200 m

User program can control the

interface

Yes

The interface can trigger a break or

an interrupt in the user program

Yes (message with break ID)

Protocol driver

3964 (R); ASCII and RK512

Programming

CPU 314C-2 PtP

CPU 314C-2 DP

Programming language

LAD/FBD/STL

Available instructions

see the Instruction List

Nesting levels

8

System functions (SFCs)

see the Instruction List

System function blocks (SFBs)

see the Instruction List

User program security

Yes

Integrated I/O

CPU 314C-2 PtP

CPU 314C-2 DP

Default addresses of the integrated

Digital inputs

Digital outputs

Analog inputs

Analog outputs


124.0 to 126.7
124.0 to 125.7
752 to 761
752 to 755