3.3 S7 connections

CPU 31xC and CPU 31x, Technical data

3-30

Manual, Edition 08/2004, A5E00105475-05

Availability of connection resources

Table 3-11 Availability of connection resources

Reserved for

CPU

Total number

connection

resources

PG

communication

OP communication S7 basic

communication

Free

S7 connections

312C

6

1 to 5, default 1 1 to 5, default 1

0 to 2, default 2

313C

313C-2 PtP

313C-2 DP

8

1 to 7, default 1 1 to 7, default 1

0 to 4, default 4

314C-2 PtP

314C-2 DP

12

1 to 11, default

1

1 to 11, default 1

0 to 8, default 8

312

6

1 to 5, default 1 1 to 5, default 1

0 to 2, default 2

314

12

1 to 11, default

1

1 to 11, default 1

0 to 8, default 8

315-2 DP

315-2 PN/DP

16

1 to 15, default

1

1 to 15, default 1

0 to 12, default 12

317-2 DP

317-2 PN/DP

32

1 to 31, default

1

1 to 31, default 1

0 to 30, default 0

Displays all non-

reserved S7

connection resources

as free connection

resources.

Note
When using a CPU 315-2 PN/DP, you can configure up to 14 connection resources for

S7 communication in NetPro: These connections are then reserved. When using a

CPU 317-2 PN/DP, you can configure up to 16 connection resources for S7 communication

in NetPro.