Communication

3.2 Communication services

CPU 31xC and CPU 31x, Technical data

3-8

Manual, Edition 08/2004, A5E00105475-05

Reference

Details on SFCs are found in the

Instruction list, for more details refer to the

STEP 7 Online Help or to the System and Standard Functions Reference Manual.

For further information on communication, refer to the

Communication with SIMATIC

manual.

3.2.5

S7 communication

Properties

A CPU can always operate in server or client mode in S7 communication: We distinguish

between

communication with unilateral configuration (for PUT/GET only)

communication with bilateral configuration (for USEND, URCV, BSEND, BRCV, PUT,

GET)

However, the functionality depends on the CPU. A CP is therefore required in certain

situations.

Table 3-3

Client and server in S7 communication, using connections with unilateral / bilateral

configuration

CPU

Use in server mode for

connections with unilateral

configuration

Use in server mode for

connections with bilateral

configuration

Use as client

31xC >= V1.0.0 Always possible at the

MPI/DP interface, without

programming the user

interface

Only possible with CP

and loadable FBs.

Only possible with CP

and loadable FBs.

31x >= V2.0.0

Always possible at the

MPI/DP interface, without

programming the user

interface

Only possible with CP

and loadable FBs.

Only possible with CP

and loadable FBs.

31x >= V2.2.0

Always possible at the

MPI/DP interface, without

programming the user

interface

Possible at PN

interface with

loadable FBs, or

with CP and loadable

FBs.

Possible at PN

interface with

loadable FBs, or

with CP and

loadable FBs.

The user interface is implemented using standard function modules (FBs) from the standard

library of STEP 7, under communication blocks.

Reference

For further information on communication, refer to the

Communication with SIMATIC

manual.